What is the meaning of kcmil?
thousands of circular mils
Glossary Term: kcmil
MCM is an abbreviation for thousands of circular mils, an old measurement of wire gauge. 1 MCM = 1 kcmil = 0.5067 square milimeters. A mil is 1/1000 inch. A wire 200 mils in diameter is 40 MCM.
What size is kcmil?
0.5067 mm²
kcmil—In the North American electrical industry, conductors larger than 4/0 AWG are generally identified by the area in thousands of circular mils (kcmil), where 1 kcmil = 0.5067 mm². A circular mil is the area of a wire one mil in diameter.
What size wire is 400 kcmil?
202.7 mm2
kcmil Wire Size Chart (Copper Wire)
kcmil or MCM Wire: | mm2 (Diameter): | Ampacity At 90°C (194°F): |
---|---|---|
400 kcmil (400 MCM) | 202.7 mm2 | 380 Amps |
500 kcmil (500 MCM) | 253.4 mm2 | 430 Amps |
600 kcmil (600 MCM) | 304.0 mm2 | 475 Amps |
700 kcmil (700 MCM) | 354.7 mm2 | 520 Amps |
Is 250 mcm the same as 250 kcmil?
250 MCM wire can also be denoted as 250 kcmil wire; these are exactly the same wires.
What kcmil 250?
For example, one common wire size used in the NEC has a cross-section of 250,000 circular mils, written as 250 kcmil or 250 MCM, which is the first size larger than 0000 AWG used within the NEC.
What is KCM of a conductor?
KCMil – A method of measuring conductor size that stands for thousand circular mils. K represents kilo for 1,000. C represents circular, and mil, M, is 1/1000 of an inch. A wire that is one mil in diameter has an area of one circular mil or 1 KCMil. KCMil replaced MCM for sizing conductors.
What size is 250 kcmil?
Standard sizes
Area | NEC copper wire ampacity with 60/75/90 °C insulation (A) | |
---|---|---|
(kcmil, MCM) | (mm2) | |
250 | 126.7 | 215 |
300 | 152.0 | 240 |
350 | 177.3 | 260 |
What is the diameter of 250 kcmil wire?
Outside Diameter: 0.720 inches.
Is 500 mcm the same as 500 kcmil?
kcmil (or MCM; it’s the same) stands for thousands of circular mils.
…
kcmil To AWG Chart (1st MCM To AWG Chart)
kcmil Wire (Or MCM Wire): | AWG Wire: |
---|---|
350 kcmil (350 MCM) | -6.17 AWG |
400 kcmil (400 MCM) | -6.75 AWG |
500 kcmil (500 MCM) | -7.71 AWG |
600 kcmil (600 MCM) | -8.49 AWG |
Is AWG the same as kcmil?
Kcmil sizes are used instead of AWG for sizes larger than 4/0 AWG. The smallest standard size is 250 kcmil, the largest 2000 kcmil.
How many amps is 250 kcmil good for?
Related Resources
Size | Temperature Rating of Copper Conductor | |
---|---|---|
(AWG or kcmil) | 60°C (140°F) | 90°C (194°F) |
4/0 AWG | 195 | 260 |
250 KCMIL | 215 | 290 |
300 KCMIL | 240 | 320 |
How is kcmil calculated?
The n gauge wire’s cross sectional area An in kilo-circular mils (kcmil) is equal to 1000 times the square wire diameter d in inches (in). The n gauge wire’s cross sectional area An in square inches (in2) is equal to pi divided by 4 times the square wire diameter d in inches (in).
What size wire is 300 kcmil?
250 kcmil wire converts to -4.72 AWG wire, for example.
kcmil To AWG Chart (1st MCM To AWG Chart)
kcmil Wire (Or MCM Wire): | AWG Wire: |
---|---|
250 kcmil (250 MCM) | -4.72 AWG |
300 kcmil (300 MCM) | -5.51 AWG |
350 kcmil (350 MCM) | -6.17 AWG |
400 kcmil (400 MCM) | -6.75 AWG |
How is Kcmil calculated?
What Kcmil 250?
What size wire is 250 kcmil?
The smallest kcmil wire is a 250 kcmil wire.
It has a 126.7 mm2 cross-section and a median ampacity of 255 amps (copper wire at 75°C, according to NEC ampacity charts). 250 kcmil wire converts to -4.72 AWG wire, for example.
What size wire is 1000 kcmil?
Standard sizes
Area | NEC copper wire ampacity with 60/75/90 °C insulation (A) | |
---|---|---|
(kcmil, MCM) | (mm2) | |
900 | 456.0 | 435 |
1000 | 506.7 | 455 |
1250 | 633.4 | 495 |
How many amps can 350 kcmil carry?
Related Resources
Size | Temperature Rating of Copper Conductor | |
---|---|---|
(AWG or kcmil) | 60°C (140°F) | 75°C (167°F) |
250 KCMIL | 215 | 255 |
300 KCMIL | 240 | 285 |
350 KCMIL | 260 | 310 |
How do you convert kcmil to MM?
1 kcmil is equal to 0.5067 mm2.
What size is 750 kcmil?
Standard sizes
Area | NEC copper wire ampacity with 60/75/90 °C insulation (A) | |
---|---|---|
(kcmil, MCM) | (mm2) | |
700 | 354.7 | 460 |
750 | 380.0 | 475 |
800 | 405.4 | 490 |
What is the diameter of 350 kcmil wire?
Specifications: Size AWG: 350. Weight per 1,000 ft: 1165 lbs. Outside Diameter: 0.830 inches.
Is kcmil aluminum or copper?
Product Overview. Hyplug™ aluminum compression adapter with Pentrox® for 250 (Aluminum) kcmil; 250 Str (Copper) kcmil wire. The adapter is made of aluminum with 2.98 inch length and . 47 inch plug diameter.
What gauge wire is 10mm2?
American Wire Gauge (AWG) vs. cross sectional area converter.
American Wire Gauge (#AWG) | Diameter (inches) | Cross Sectional Area (mm2) |
---|---|---|
9 | 0.114 | 6.63 |
10 | 0.102 | 5.26 |
11 | 0.0907 | 4.17 |
12 | 0.0808 | 3.31 |
Is AWG same as gauge?
Both Gauge and AWG are ideally the same. When writing, we call it a gauge for clear understanding. AWG measurements do not consider the insulation of the conductor. The higher the AWG number, the smaller the conductor.
How do I calculate wire size?
How do I calculate wire size for motors?
- Multiply the resistivity (Ω•m) of the conductor material by the peak motor current (A), the number 1.25, and the total length of the cable (m).
- Divide the result by the voltage drop from the power source to the motor.
- Multiply by 1,000,000 to get the result in mm2.